Creepage Enquire

Application · indoor enclosures

Terminating into switchgear panels and compact cable boxes

Decide what insulation is added inside the enclosure. Inputs: cable construction, conductor mm², Umax, and the bushing centre distance off the panel general arrangement.

The constraint that defines the job

A panel gives a termination no room. Bushing centres are fixed by the switchgear maker, and the manufacturer's three protector charts publish them at 95 mm for the GTPE-1 elbow and at 110 mm and 125 mm for the 12 kV and 24 kV boot pairs. At that spacing, clearance inside the box sits below what the same voltage would be given in open air.

Insulation is therefore added, not assumed. The published reasons for fitting it are specific: flashover under high humidity, rodent or bird intervention, and surge impulse.

Two inputs come off the cable schedule — construction and conductor cross-section. Two come off the panel drawing — Umax and the gland-plate-to-bushing dimension. Miss the fourth and no tail length can be specified, which makes the kit code a guess.

By enclosure: what is terminated, and what is added

Read the first column off the general arrangement. The rest follows from it.

Enclosure on the drawingTermination methodInsulation added insidePublished figure that governs it
Switchgear panel with a cable boxIndoor heat-shrink kit, GXE or GPE codeRight-angle or straight boot over each bushing connectionNo tracking or erosion up to 3.25 kV for 20 minutes [ASTM D2303]
Compact entry box or motor terminal boxIndoor heat-shrink kit sized on the cable scheduleEPDM barrier system: boot, grommets and plugBushing centre distance 95 mm (GTPE-1), 110 mm at 12 kV, 125 mm at 24 kV
Ring main unit with a type C bushingScreened separable connector, plugged onNone — the connector body carries its own earthed screen630 A to 24 kV, 630/1250 A to 36 kV, to IEC 60502.4
Draw-out breaker cubicleNot a cable termination at allInsulation boot over the breaker's draw-out contactsDielectric strength 25 kV/mm minimum [IEC 243], meeting ANSI C37.20.2

What three of the answers look like

Tail length is set by the panel, not by the kit

Tail length is the one kit dimension the panel drawing decides. Measure gland plate to bushing palm, add the lug barrel, then compare that against the published indoor cut before any code is raised.

GXOS/E-1236 publishes indoor tails of 450 mm at 12 kV, 550 mm at 24 kV and 700 mm at 36 kV, and the GXO/E series publishes special tail lengths as available on request — the route when the cable box is deeper than the standard cut. Series-by-series figures are tabulated on indoor or outdoor termination.

A short tail is not recoverable with what is in the van. A long one is bent into the box, and the bend eats the clearance the boots were bought to protect.

Sources disagree — straight or right angle

The Cable Terminal Protector page describes the system as insulating right-angle connections, then publishes two selection charts on that same page: a straight pair, GSTB-1 and GSTB-2, alongside the right-angle GRTB-1 and GRTB-2. Both are reproduced as published, neither averaged. A panel presenting straight bushing palms needs the profile confirmed in writing against the code.

The draw-out breaker on the same requisition

A breaker cubicle is not a cable termination, but it sits in the same lineup and is routinely left out until the type-test clause is drafted. Published properties of the insulation boot for draw-out circuit breakers:

  • Non-tracking cross-linked polyolefin, halogen free and flame retardant; oxygen index ≥ 28 [IEC 93]
  • Dielectric strength 25 kV/mm minimum [IEC 243]
  • Continuous temperature limit −40 to +105°C [IEC 216]
  • No tracking, erosion or flame failure up to 3.25 kV for 20 minutes [ASTM D2303]
  • Resists acid, alkali and salt corrosion, and stated to be highly resistant to UV and ozone, so one part covers indoor and outdoor cubicles
  • Fitted or stripped in minutes, complete with fasteners, as often as required — meets ANSI C37.20.2, cited from the manufacturer's page

Not published — ask the manufacturer

Both boot profiles are fully dimensioned — supplied and recovered bore, leg lengths and wall thickness, reproduced on bushing boots — but no voltage figure is published against any boot code, so a GRB-2A cannot be argued onto a 24 kV board from the chart alone. Nor is any pollution class stated for the boots or the barriers, and no creepage distance is published for either. Send the bushing outside diameter, the lug width, the phase centre distance and Um, and ask for the size and the class confirmed together.

Where the job hands off

A ring main unit is a switchgear panel with a different cable interface. Once the drawing shows a type C bushing the answer set changes: the connector makes the termination and carries its own earthed screen, so nothing is fitted over it. One figure does not carry across — the GTPE-500 elbow fits RMU type C bushings and is charted at 95 mm centres, but it is stated not to be a touch-proof product, so it answers a clearance problem and never a dead-front clause. See RMU cable terminations.

The barrier system also names motor terminal boxes and distribution transformers among its applications, so the part is unchanged there; what changes is the equipment side and the earthing around it, at transformer and motor terminations.

Questions raised at the panel-drawing stage

Does a bushing boot change the termination's type-test result?
No. A boot covers a connection, it does not make one, and withstand figures are published against the kit as supplied. Class figures by voltage are tabulated on the type test chart.
Can the terminal be voltage-tested once the insulation is fitted?
GSTB/GRTB and GTPE-500 are both published as facilitating direct voltage testing and as re-usable. The GRB and GSB heat-shrink boots are not published as re-usable. That makes it a specification-time decision, because a shrunk-on boot cannot be lifted for a test and refitted.
Is a terminal protector touch-proof?
No. The GTPE-500 document says in as many words that it is not a touch-proof product. That duty belongs to the screened separable connector, published with an earthed outer conductive screen of 5000 Ω or less.
The panel is indoors and dry. Is anything needed beyond the indoor kit?
That is decided by the bushing centres, not by the room. Where the box is roomy and dry, the indoor kit alone is the honest answer, and nothing on this page argues otherwise. The full component list sits at termination kit components.

Send the panel GA alongside the cable schedule

This job is specified from two drawings at once, and an enquiry carrying only one comes back as a question. Bushing centre distance and the gland-plate-to-bushing dimension are the two figures almost always missing.