Creepage Enquire

Guide

Cable joint or cable termination? What each kit actually does

Decide it from the far end of the cable — another cable end, or open air. Every component in the box follows from that one input.

The decision, and the input data it needs

Two facts settle this before a kit code is written down: what the cable end being worked on meets, and whether it stays enclosed afterwards. Meeting another cable end is a joint. Meeting a bushing, a lug, a busbar or an overhead line is a termination.

A joint puts the cable back the way the cable maker built it — ferrule, insulation, screen, armour or lead-sheath continuity, outer jacketing sleeve. When the crew packs up the field is still inside a cable and no part of the splice sees weather.

A termination does the reverse. It opens the cable, cuts the screen back, grades the field across that cut, then hands the field to air. Both operations sit under one heading in the manufacturer's index of heat shrinkable cable joints and terminations, which is where the confusion in the search box begins.

Joint and termination, item by item

Read down the column for the operation being quoted. Series names are the manufacturer's own; the termination side is set out by construction on XLPE and EPR, PILC and 1.1/3.3 kV.

What differsCable jointCable termination
Cable end meetsAnother cable endA bushing, lug, busbar or overhead line
Kit rebuildsInsulation, screen, armour or sheath continuity, outer sheathInsulation to the lug, the screen cut-back, the weather surface
Conductor connectionInline ferrule, crimping or barrier typeTerminal lug with lug sealing mastic
Field grading partStress control tubing and mastic each side of the ferruleStress control tubing over the screen cut-back, one per core
Creepage partsNoneNon-tracking weather-resistant tubing, plus rain sheds outdoors
Mechanical protectionWraparound metallic joint case, or GI mesh tapeNone — the cores stand as tails, 450 mm to 900 mm
Extruded cable seriesGXS/1236 for 3-core, GXSS-1236 for single coreGXO/E-1112 to 3336 for 3-core, GXOS/E-1236 for single core
Paper cable seriesGPS/1112, GPS/2436GPO/E-1112, GPO/E-1524, GPO/E-3336
1.1 and 3.3 kV seriesGXLT/GPLTGLT-1100
Two constructions at onceGTJ/1112 and GTJ/2436, PILC to XLPENot applicable — one construction per end
AC withstand at 1.1 / 3.3 kV3.5 kV / 6 kV for 5 minutes, immersed in water4 kV / 8 kV for 15 minutes, dry

Why the air interface is the harder half

Everything a joint resists is bounded: buried or ducted, its temperature swing the cable's own, its mechanical load carried by the joint case. The test conditions say so. GXLT/GPLT is given AC 3.5 kV and 6 kV held 5 minutes with the joint immersed in water; GLT-1100, covering the same two voltages, is tested dry at 4 kV and 8 kV for 15 minutes.

A termination has no such boundary. Once the field crosses into air a surface holds it off, and a surface ages — it wets, it collects salt and cement dust, leakage current dries bands into it, and tracking starts at the driest band. Two components exist for that alone: the non-tracking weather-resistant sleeve and the rain shed, which lengthens the leakage path without lengthening the termination.

The screen cut-back is the shared problem. Cutting a metallic screen concentrates the field at the cut edge, so both families carry stress control tubing and mastic for it. Everything else in the two boxes diverges.

Sources disagree

The single-core joint sheet (GXSS-1236) and the single-core termination sheet (GXOS/E-1236) publish the same DC withstand voltages — 48 kV, 96 kV and 144 kV for the 12 kV, 15–24 kV and 36 kV systems — but the joint is given as 30 minutes and the termination as 1 minute. Both are reported here as published, not averaged. Settle the duration in writing before it is copied into a type-test clause.

The two families, by series

GXLT/GPLT — joint
Straight-through, 1 to 4-core extruded or paper cable, armoured or unarmoured, 1.1 and 3.3 kV. The only kit sheet in either family naming a compliance set: IEC 60502, IEC 60060, IEC 60230.
GXS/1236 — joint
3-core XLPE/PVC, one family from 12 kV to 36 kV.
GXSS-1236 — joint
The single-core counterpart to GXS, extruded dielectric and shielded, to 36 kV.
GPS/1112, GPS/2436 — joint
3-core PILC: 11 kV at Umax 12 kV, then screened paper cable to 33 kV.
GTJ/1112, GTJ/2436 — joint
Transition joints. PILC one side, XLPE the other, matched component for component.
GXLTS — joint
Straight-through joints for submersible cable.
GLT-1100 — termination
1, 2, 3, 3½ and 4-core extruded or paper cable at 1.1 and 3.3 kV. Outdoor GLT-01 to GLT-05, indoor GLT-11 to GLT-15, and no stress control component at all.
GXO/E-1112 · 1524 · 3336 — termination
3-core XLPE/EPR shielded cable at 12, 24 and 36 kV. Outdoor codes read GXO, indoor GXE; indoor kits ship without rain sheds.
GXOS/E-1236 — termination
Single-core XLPE/EPR/PVC to 36 kV, 16 to 1000 mm². Outdoor rain sheds run 2, 3 and 4 per core at 12, 24 and 36 kV.
GPO/E-1112 · 1524 · 3336 — termination
Screened, lead-sheathed or armoured PILC at 12, 24 and 36 kV. Outdoor GPO, indoor GPE, plus an oil barrier sleeve and an earthing plumb bonding lead sheath to armour.

Straight-through, transition, and where joints are covered properly

A straight-through joint sees one cable construction on both sides. A transition joint sees two, and on a requisition that is the only difference worth writing: GTJ/1112 to 12 kV, GTJ/2436 for the 24 kV and 36 kV classes, PILC facing XLPE, with a barrier-type inline connector, stress relief mastic and an oil barrier sleeve where the paper side needs one. It remains a joint, and cannot stand in for a termination at either end.

Joint kit codes, conductor ranges and component counts are deliberately not tabulated here. They are set out for the GXLT, GXS, GXSS, GPS and GTJ series on cablejointkit.com, a sister reference from the same publisher working off the same manufacturer's catalogue; this page carries only the boundary.

Not published — ask the manufacturer

Withstand figures are published for every family, but not in the same place. The manufacturer's web pages carry them for GXO/E-1112 and for the single-core kits and omit them entirely for GXO/E-1524 and GXO/E-3336; the catalogue carries all of them. At 24 kV the like-for-like comparison is available and worth making: the GXO/E-1524 termination and the GXS/1236 joint are both published at AC 50 kV for 1 minute, DC 96 kV, 125 kV impulse and discharge extinction above 25.4 kV below 5 pC. The joint and the termination are qualified to the same numbers. What is genuinely not published is a report number, laboratory or date against any individual kit code on either side — the figures are stated as requirements met, not as certificates. Ask for the report before a clause is drafted around them.

"Termination joint" is not a product type

The phrase resolves to at least four different requisitions. Sort it by what the enquiry names.

  • Two cable ends and no equipment named — a joint, one kit per drum join, sized on conductor area and construction.
  • One cable end plus a bushing, a lug, a busbar or a line — a termination. Indoor or outdoor changes the kit code, not the family.
  • A PILC feeder being extended in XLPE — a transition joint, GTJ series, with no termination at either side of that splice.
  • Both operations on one feeder — one joint kit per drum join and one termination kit at each end of the run, never a single combined line item.
  • Armour clamped where the cable enters a panel, with nothing done to the field — a gland, which is neither.

The gland is neither

A gland is a mechanical fitting: it anchors the cable at an enclosure wall, terminates the armour and seals the sheath entry. It grades no field, adds no creepage and restores no insulation, so no kit code in either range is a gland size. Exactly one gland-named item appears in the published kit contents of either family — the adhesive-lined gland sleeve supplied with GXOS/E-1236 for armoured single-core cable, and it seals rather than clamps. On the 3-core kits a constant force spring or worm drive clip picks the armour up and a tinned copper braid carries it away. Schedules write glanding and termination on one line because the jobs fall in the same hour, not because they are one product.

Questions the two words cause

Do a joint kit and a termination kit for the same cable share components?
Several. Stress control tubing and mastic, tinned copper earth braid, worm drive clips and mastic sealing tape appear in both, and the oil barrier sleeve crosses over on paper cable. What never crosses is the inline ferrule and the joint case on one side, and the terminal lug, non-tracking weather sleeve and rain sheds on the other. Itemised: every component in a termination kit.
Are joints and terminations type-tested to the same voltages?
At a given class the published voltages line up: at 12 kV the GPS/1112 joint, the GTJ/1112 transition joint and the GXO/E-1112 termination each carry AC 35 kV for 1 minute, DC 48 kV for 30 minutes and a 75 kV impulse. Conditions are what separate them, sharply at 1.1/3.3 kV — immersed for the joint, dry for the termination. Class by class: withstand voltages in one table.
Do either of these ranges go above 36 kV?
No. The published joint and termination kits stop at 36 kV in both the extruded and the paper families, and nothing in the catalogue terminates a 66 kV cable. The only 66 kV item published is a busbar sleeve, which is not a cable accessory: what the 36 kV ceiling means.

Send the cable make-up, not the kit code

Five inputs settle either family: insulation (XLPE/EPR, PILC or PVC), core count, conductor area in mm², Umax, and indoor or outdoor. With those in the first message a kit code comes back in one reply instead of four.