Compare
Indoor or outdoor termination: what actually changes in the kit
Inputs required: cable insulation, core count, conductor mm², Umax, and one binary that fixes the part number before the requisition is raised.
Three line items change. The electrical system does not.
Read against the published kit contents for the GXO/E, GPO/E, GXOS/E and GLT series, 1.1 kV to 36 kV.
| Element of the kit | Outdoor variant | Indoor variant |
|---|---|---|
| Part number | GXO, GPO or GXOS prefix; GLT-0x at LV | GXE, GPE or GXES prefix; GLT-1x at LV — see the note on that pair |
| Rain sheds | Fitted; 2, 3 or 4 per core at 12, 24 and 36 kV | None at 12 kV; 1 per core at 24 kV; 2 per core at 36 kV |
| Standard tail length | 600 to 900 mm by series and voltage class | 450 to 700 mm by series and voltage class |
| Stress control | Stress control tubing, plus stress control mastic on GXOS/E | Identical |
| Outer surface layer | Non-tracking weather-resistant tubing | Identical |
| Screen and armour earthing | Tinned copper braid and worm drive clips; earthing plumb on PILC kits | Identical |
| Lug and sealing | Terminal lug, lug sealing mastic, adhesive-lined terminal sleeve | Identical |
| Withstand voltages | Published against the voltage class; plus a wet AC withstand, an immersion test and 1000 h salt fog | Same class figures; a 300 h humidity test instead of salt fog and immersion |
What the code letter actually buys
Across the heat-shrink termination range manufactured by Gala Thermo Shrink Pvt. Ltd., the indoor and outdoor forms of one kit share a bill of material and part company on three line items: how many rain sheds are in the box, how long the cut tails are, and which code is printed on the label.
Nothing in the stress-grading system moves. Stress control tubing, the adhesive-lined terminal sleeve, the non-tracking weather-resistant outer tubing, the cable breakout, the tinned copper earth braid and the worm drive clips appear on both lists in the same quantities. On the paper-insulated kits the oil barrier sleeve, glass cushion tape and the earthing plumb that bonds lead sheath to armour are common to both as well.
The kit pages publish one set of withstand figures per voltage class and do not split them by mounting. The type-approval sequence does split them, and it is the only published place that separates the two. Outdoor terminations take an AC high voltage test wet, one minute at 25.4, 51 and 76 kV; an immersion test of ten cycles; and a salt fog test of 1000 hours at 1.25 × U0. Indoor terminations take a 300-hour humidity spray instead, at 8, 16 and 24 kV AC. Both take the 60-cycle heating run in air. The full sequence is tabulated on the termination type test chart.
Tail length is the figure that has to reach the drawing
Tail length sets how far the cores run from the breakout to the lug, so it is the number that must agree with the switchgear general arrangement before anything is ordered. The ladder is the same on all three three-core families and on the single-core one: 600, 800 and 900 mm outdoor at 12, 24 and 36 kV, against 450, 550 and 700 mm indoor. The indoor tail is shorter by 150 mm at 12 kV, 250 mm at 24 kV and 200 mm at 36 kV.
Special tail lengths are published as available on request on the GXO/E series, which is the route when the gland plate to bushing dimension does not suit the standard figure — see the manufacturer's GXO/E-1524 page for that kit's full contents list.
Published standard tail lengths
| Series | Cable and voltage class | Outdoor tail | Indoor tail |
|---|---|---|---|
| GXO/E-1112 | 3-core XLPE/EPR, 12 kV | 600 mm | 450 mm |
| GXO/E-1524 | 3-core XLPE/EPR, 24 kV | 800 mm | 550 mm |
| GXO/E-3336 | 3-core XLPE/EPR, 36 kV | 900 mm | 700 mm |
| GPO/E-1112 | 3-core PILC, 12 kV | 600 mm | 450 mm |
| GPO/E-1524 | 3-core PILC, 24 kV | 800 mm | 550 mm |
| GPO/E-3336 | 3-core PILC, 33/36 kV | 900 mm | 700 mm |
| GXOS/E-1236 | Single-core, 12 kV | 600 mm | 450 mm |
| GXOS/E-1236 | Single-core, 24 kV | 800 mm | 550 mm |
| GXOS/E-1236 | Single-core, 36 kV | 900 mm | 700 mm |
| GLT-1100 | 1.1 and 3.3 kV, 1 to 4-core | Not published | Not published |
Figures from the catalogue's accessories notes on each kit page. Where the manufacturer's website differs on the two upper GXO/E classes, see the note below. Special lengths are stated as available on request across the range.
Kit code pairs and conductor range
| Series and class | Outdoor codes | Indoor codes | Conductor range |
|---|---|---|---|
| GXO/E-1112, 12 kV | GXO-11 to GXO-15 | GXE-11 to GXE-15 | 16 to 500 mm² |
| GXO/E-1524, 24 kV | GXO-21 to GXO-24 | GXE-21 to GXE-24 | 16 to 400 mm² |
| GXO/E-3336, 36 kV | GXO-31 to GXO-34 | GXE-31 to GXE-34 | 25 to 400 mm² |
| GPO/E-1112, 12 kV | GPO-11 to GPO-15 | GPE-11 to GPE-15 | 16 to 500 mm² |
| GPO/E-1524, 24 kV | GPO-21 to GPO-24 | GPE-21 to GPE-24 | 25 to 500 mm² |
| GPO/E-3336, 33/36 kV | GPO-31 to GPO-34 | GPE-31 to GPE-34 | 35 to 400 mm² |
| GXOS/E-1236, to 36 kV | GXOS | GXES | 16 to 1000 mm² |
| GLT-1100, 1.1 and 3.3 kV | GLT-01 to GLT-05 | GLT-11 to GLT-15 | 4×16–35 to 4×400–500 mm² |
The outdoor and indoor codes are separate part numbers with different contents; they cannot be substituted after despatch.
Rain sheds per termination, as published
| Series | Outdoor | Indoor |
|---|---|---|
| GXO/E-1112, 12 kV | 6 per kit, 2 per core | None |
| GXO/E-1524, 24 kV | 9 per kit, 3 per core | 1 per core |
| GXO/E-3336, 36 kV | 12 per kit, 4 per core | 2 per core |
| GPO/E-1112, 12 kV | 6 per kit, 2 per core | None |
| GPO/E-1524, 24 kV | 9 per kit, 3 per core | 1 per core |
| GPO/E-3336, 33/36 kV | 9 per kit, 3 per core | 2 per core |
| GXOS/E-1236, 12 kV | 2 | None |
| GXOS/E-1236, 15–24 kV | 3 | 1 |
| GXOS/E-1236, 36 kV | 4 | 2 |
Outdoor figures are the catalogue's Qty. column, which counts sheds per kit; the per-core figure follows by dividing by three on the three-core kits.
Not published — ask the manufacturer
Two figures a specifier needs here and cannot source. GLT-1100 publishes no standard tail length at all, indoor or outdoor, so the one family that covers both cable constructions is also the one with no dimension to check against a drawing. And no pollution class is mapped to either variant, so the word 'indoor' carries no published environmental qualification — a coastal switchroom and a sealed panel take the same code. Confirm both in writing before either enters a specification clause.
Sources disagree — the tail length ladder
The catalogue and the website give different tail lengths for the same kits. The catalogue runs one ladder across every three-core family: 600, 800 and 900 mm outdoor and 450, 550 and 700 mm indoor at 12, 24 and 36 kV. The manufacturer's web pages for GXO/E-1524, GXO/E-3336 and GPO/E-3336 instead repeat the 12 kV page's 600 mm and 450 mm, and the GXO/E-3336 page's own description text still names the 1524 series — so those pages read as copies of the 12 kV page rather than as a second measurement. The table above follows the catalogue, and says so. Both figures are reported and neither is averaged, but a 300 mm error in tail length is not recoverable on site, so confirm the figure against the kit code before the cable-box height is fixed.
A rain shed is a creepage component, not an outdoor badge
The shed supplied in these kits is INSULSHED, cross-linked polyolefin with non-tracking behaviour, internally coated with water-resistant mastic and described by the manufacturer as suitable for indoor and outdoor applications alike. Its figures do not change with where it is fitted: no tracking, erosion or flame failure up to 3.25 kV for 20 minutes [ASTM D2303], dielectric strength 15 kV/mm minimum [ASTM D149], volume resistivity 1 × 10¹⁴ ohm.cm minimum [ASTM D257], shrink temperature 125°C and a continuous limit published as −40°C to +100°C on the datasheet and +110°C on the product page [IEC 216]. Ten sizes are charted, GRS 130-1 to GRS 130-6 with four N and S variants between them, published on the creepage extension skirt page.
That matters for the case the code letter cannot express. A termination inside a coastal switchroom, a cement or fertiliser plant, or a naturally ventilated substation beside a haul road collects salt, dust and conductive deposit across the same surface an outdoor one does, minus the rain that periodically washes it off. A sealed, air-conditioned panel collects almost none. Both are 'indoor'.
Where the switchroom is dirty, the creepage extension can be specified on its own rather than by changing the kit — sizes, and the tri-core GRST-1 to GRST-3 variant that fits over three cores at once, are set out under rain sheds. That judgement is the specifier's to make and to record.
The call is made at requisition, not on site
GXO-23 and GXE-23 are different part numbers holding different contents. A crew that opens an indoor box at an outdoor termination has no rain sheds and 150 mm less tail than the drawing assumes, and neither shortfall is recoverable with what is in the van. So indoor or outdoor belongs in the cable schedule next to insulation type, core count, mm² and Umax, before the requisition leaves the office.
For a first cut by construction rather than by voltage, XLPE and EPR kits, PILC kits and LV kits at 1.1 and 3.3 kV each list their own code pairs, and what is in the box itemises the components both variants share.
Questions this decision raises
Which part of the code means indoor?
Can rain sheds simply be added to an indoor kit?
Do the two variants have different withstand voltages?
Is there an indoor or outdoor termination at 66 kV?
Is any termination in the range supplied without the split?
Getting a part number back on the first reply
Send the cable make-up, core count, conductor mm², Umax and the indoor or outdoor call in one line, plus the tail length the drawing needs if it is not the standard figure.